Features
◆Ambient temperature -10~83℃
◆Easy Zero / Span adjustment.
◆Easy maintenance
Spec◆Ambient temperature -10~83℃
◆Easy Zero / Span adjustment.
◆Easy maintenance
Specification | WP200 – Double Acting |
Input signal | 20~100kPa |
Supply air pressure | 0.14~0.7MPa(140~700kPa) |
Stroke | 125mm |
Air connection | Standard:Rc1/4(Pressure gauge Rc1/8) Option:NPT1/4(Pressure gauge NPT1/8) |
Pressure gauge | Standard:0~0.2MPa、0~0.4MPa、0~1.0MPa Option:kpa, psi *,bar |
Cam | Standard: Linear Option:Non-Linear |
Ambient temperature | Standard:-10~83℃ |
Weight | Approx.8.0㎏ |
Material | Body / cover : Aluminum diecasting (specially annodized |
Linearity | ±3.5% |
Hysterisys | 2.0% |
Repeatability | 1.0% |
Sensitivity | 1.0% |
range of supply air | 0.3%/0.0Mpa |
tolerance by posture | 10°:0.5% / 90°:1.0% |
vibration resistance | 1%/1G |
Air consumption | 10Nℓ/min At SUP 0.4MPa and Output75% balancing |
Output air capacity | 140/min At SUP 0.4MPa |
Balancing pressure | 75% |